@thesis{thesis, author={Mauriraya Kartika Tresya and Syafitri Uray Nur Intan}, title ={PERHITUNGAN RUGI DAYA PADA PENYULANG ARKEOLOGI JARINGAN DISRIBUSI TEGANGAN MENENGAH 20kV DI PT. PLN UP3 SERPONG}, year={2019}, url={http://156.67.221.169/1787/}, abstract={The community?s need for electrical energy continues to increase along with the increase in lifestyle and the equipment used. This condition makes PT.PLN (Persero) must be able to channel electricity and requires the availability of efficient and quality electrical energy. Efficient in the sense of the energy produced can be used maximally by the customer or not equipment. Ehwn distributing an electric power system there must be constraints such as losses and voltage drops. Losses and voltage drop are caused by the length and breadth of the load resulting in the distribution of electrical power, especially in problems with power losses and voltage drop. The power losses in Archeology feeders during the Peak Load Time and Peak Load Time are at SR242 substations 0,21% & 0,26% while SRP136 0,11% & 0,10%. The resulting value of voltage drop is 19,4380kV which is still whithin the tolerance range of ±10% of 20kV, so that Archeology feeders do not need to change the conductor.} }