@thesis{thesis, author={Anggraini Windri Triluvi and Hariyati Rinna}, title ={PENGARUH RECONNECTING SAMBUNGAN RUMAH PADA GARDU SP264 TERHADAP JATUH TEGANGAN DAN RUGI DAYA DI PT.PLN (PERSERO) UP3 KEBON JERUK}, year={2019}, url={http://156.67.221.169/1811/}, abstract={Distribution systems are divided into primary and secondary distribution networks. Primary distribution network better known as medium voltage network is a network of substation (GI) transformers to distribution substations, while secondary distribution networks or low voltage networks are channel networks from distribution substation transformers to customers or loads. Distribution network is part of the power system closest to the customer or load. In this study, the author focuses on the problem of comparing the measurement of the tap connector with the Compression Connector (CCO) connection between Low Voltage Network (JTR) and house connection (SR). The measurement results are used to calculate voltage drops and power losses per pole. With the same direction for low voltage airways when using a tap connector, the R phase has an average power loss per pole is 652.83 Watt while using CCO is 413.33 Watts. S phase has an average power loss per pole is 233.50 Watt while using CCO is 184.92 Watts. Phase T has an average power loss per pole is 370.42 Watts while using CCO is 313.72 Watts. From the results of these calculations, indicate that when using the tap connector the losses are greater than using the CCO.} }