@thesis{thesis, author={Hariyanto Agung and Pijar Nurullah Sayyid}, title ={ANALISIS PERBAIKAN JATUH TEGANGAN PADA JTR DENGAN METODE PEMERATAAN BEBAN DI GARDU KD26A PT. PLN (PERSERO) AREA PONDOK KOPI}, year={2020}, url={http://156.67.221.169/3058/}, abstract={The voltage quality of a good electric power system must have a percentage of the voltage value that does not exceed the tolerance limit. The limits of the allowable tolerance for a voltage value are + 5% and -10% of the nominal value (SPLN 1: 1995). The long distance between the load and the distribution center and the size of the load along with the large demand for additional power and unstable loads cause problems in electricity distribution, especially voltage drops. Even distribution of loads occurs because the loading of a conductor and transformer is uneven. Repair using the load equalization method aims to reduce the voltage drop at the end of the low voltage network pole (220/380 Volt). In this thesis discusses the voltage drop at the KD 26A Distribution Substation with a major in C on transformer 2.From the results of the inspection of the tip voltage on Transformer 2 majoring C, it is obtained that the percent of voltage drop in phase R is 14.6%, phase S is 10.2%, and phase T 7.5%, then load breaking was carried out in Department C, it was obtained that the voltage drop of the R phase was 1.898%, the S phase was 1.648%, and the T phase was 1.456% which means that it has entered the tolerance limit of SPLN 1: 1995 which is + 5% and -10%.} }