@thesis{thesis, author={Kastio Putri Mayang Sari and Pujotomo Isworo and Sukmajati Sigit}, title ={Analisa Jatuh Tegangan Pada Penyulang F6 Selayo Di PT. PLN (Persero) Area Solok}, year={2020}, url={http://156.67.221.169/3112/}, abstract={The distribution system for the Selayo F6 feeder at PT. PLN Solok Area uses a radial system. In some of these channels there is a voltage drop that exceeds the standard limit of SPLN number 7 of 1987, namely 5%. In this thesis, the calculation of the amount of voltage drop, the comparison of the voltage drop with the PLN standard and the repair solution is carried out to reduce the voltage drop. From the calculation results, there were two substations that experienced a voltage drop of 1.327,605 volts with a percentage of 6,638% at the PKB-T-147 substations and 1.221,720 volts with a percentage of 6,109% at the JKB-T-152 substations. the length of the channel at the PKB-T-147 substation from a distance of 29, 84 KMS to 22 KMS and the JKB-T-152 substation from 18 KMS to 12,1 KMS. This change in distance reduces the voltage drop in the two substations with a large value of the voltage drop at the PKB-T-147 substation to 721,634 Volts with a decrease in the percentage to 3,608% and at the JKB-T-152 substation the voltage drop to 554,815 Volts decreases the percentage to 2,747%} }