@thesis{thesis, author={Diantari Retno Aita and Hariyati Rinna and Situmorang Angelly}, title ={Memaksimalkan KWh Jual Dengan Meminimalisir Ketidaknormalan Hilangnya Arus Fasa R Sistem Pengukuran Energi Dengan (Automatic Meter Reading (AMR) PT.PLN (Persero) UP3 Ciputat}, year={2020}, url={http://156.67.221.169/3431/}, abstract={Automatic Meter Reading (AMR) is a technology for collecting consumption data from an integrated energy metering device (kWh meter) from the control room via cell phone (GSM) media or radio waves using certain software. The AMR system has been applied to many customers, the AMR system can reduce abnormalities. The abnormality due to the loss of current in the R phase causes the load used by the customer to be unmeasured in the measured R phase in the AMR application for 13 days. To minimize abnormalities caused by damaged CT wiring in phase R, the CT wiring is replaced. So with the AMR system, abnormalities are avoided and bills that should be collected can be billed according to actual usage. From the application of recording and measuring the AMR system, it can also be seen that the daily load usage for 13 days of damage is 4,004.6 kWh and the use of daily loads for 13 days after the repair is 5,793 kWh, and the unmeasured load is 1788.4 kWh} }