@thesis{thesis, author={Hariyati Rinna and Syaprudin Aditya Aprialdi}, title ={PENGARUH KETIDAKSEIMBANGAN BEBAN ARUS NETRAL DAN RUGI - RUGI PADA TRAFO DISTRIBUSI DI PT PLN (PERSERO) UP3 KEBON JERUK}, year={2020}, url={http://156.67.221.169/3444/}, abstract={In meeting the electricity demand, load sharing occurs initially, but initially due to the unbalanced timing of the load, the load imbalance results in an impact on the supply of electricity. In addition to the imbalance in load usage, unbalanced connection in the R, S, and T phases is also another factor that influences the imbalance. Imbalance is what causes losses which technically will harm PLN. Losses are caused by neutral currents. The greater the value of Neutral Current during the daytime is IN = 133 A, and PN = 0.159 kW and at night the value IN = 224 A and PN = 0.451 kW, and after balancing the neutral current during the day that is IN = 195 A and PN = 0.418 kW and night time IN = 201 A and PN = 0.444 kW on transformer neutral conductors. In order to achieve a stable supply of electricity and continuity to consumers, this must be resolved} }