@thesis{thesis, author={Dwinda Ana Meylia Puspita and Erlina Erlina}, title ={PENGARUH ARUS SALURAN TERHADAP ANDONGAN DAN TEGANGAN TARIK PADA PENGHANTAR TACSR SUTT 150 KV GI CAWANG BARU – GI DUREN TIGA}, year={2021}, url={http://156.67.221.169/3655/}, abstract={The use of electricity in Indonesia makes PT PLN (Persero) must be able to meet the needs of electricity consumption in the community. The transmission line system is a support in the successful fulfillment of customer demand. SUTT 150 kV on GI Cawang Baru ? GI Duren Tiga uses a TACSR conductor. Use of TACSR conductors that are stretched between two support poles in transmission line can cause andongan and tensile stresses. According to Permen ESDM No. 18 of 2015 for a tower height of 30.7 meters, the maximum limit of andongan is 21.7 meters and based on SPLN 121 of 1996, the maximum tensile stress limit is 20% greater than the nominal wire tension. Andongan and tensile stress can be affected by line current. The line current causes heat losses resulting in increased weight on the conducting wire so that it will affect the value of the andongan and tensile stress. This study aims to find out how much influence the peak load current for andongan and tensile stresses. The results showed that the maximum andongan and tensile stress due to the peak load current occurred in July 2020 with a volume of 10,264 meters and 13,991.56 kg.} }