@thesis{thesis, author={Hariyati Rinna and Jatmiko Willy Wahyu}, title ={EVALUASI SISTEM INSTALASI BANGUNAN GEDUNG DPRD DKI JAKARTA GUNA MENCEGAH BAHAYA KELISTRIKAN}, year={2021}, url={http://156.67.221.169/3732/}, abstract={The selection of electrical installation components is very important, especially in the Jakarta Capital Region, it is noted that most of the causes of fires are due to electrical shorts. To reduce and prevent these risks, it is necessary to pay attention to the selection of safety and the type of conductor cable based on the amount of power used. In the DKI Jakarta DPRD building installation, the selection of the type of conductor has met the standards based on PUIL 2011 and SPLN 43-1: 1994, using single-core and four-core NYY conductor cables with a rated voltage of 380V. Although there are several cross-sectional conductors with an area exceeding the results of the KHA analysis, but this was done because of the possibility of an additional burden that would occur. As for the use of short-circuit and overload safety, there is the use of safety that does not meet the standard. Where on floors 2, 3 and 4 use MCB 100A, while based on the analysis carried out must use MCCB 125A. The use of short circuit safety or overload that does not meet the standards, can cause damage to the connected load in the event of an electrical disturbance.} }