@thesis{thesis, author={Kurniawan Muhammad Irwan and Pratama Putera Rizki}, title ={PENYEIMBANGAN BEBAN PADA TRAFO DISTRIBUSI DENGAN METODE PENGATURAN GRUP BEBAN DI PT. PLN (PERSERO) ULP MATTOANGING MAKASSAR SELATAN}, year={2021}, url={http://156.67.221.169/3993/}, abstract={The Distribution System is a System that direct the electricity right to the costumer, where this system really needs to ensure the continuity of the electricity supply to the costumer, which one is by ensuring the balanced load of a distribution transformator in order to minimize the losses that occur. This Skripsi is made in purpose to applying the load group setting method on a unbalanced distributing panel (PHB) and calculate the losses due to current flowing in neutral wire and material losses. The aplication of the method is based on PT. PLN (Persero) Health Index according to SPLN 17:2014 which is determined that the transformator is said to be lacking in load balance if it exceeds 20% of the percentage of the load imbalance. The unbalanced load on the distribution transformer causes current to flow in the neutral wire. On GT. MIK011 experienced an imbalance of 39,66% at Outside Peak Load Time (LWBP) and 26.33% when Peak Load Time (WBP) with neutral conductor losses of 1,839 kW at (LWBP) and (WBP) of 1,129 kW but with the application of the Regulatory Method The Load Group found a decrease in the percentage of imbalance to 16% with losses of 775.06 kW at Outside Peak Load Time (LWBP) and 15.67.% with losses to the conductor of 847.97 kW at Peak Load Time (WBP).} }