KOORDINASI EFEKTIF JARAK LIGHTNING ARRESTER PADA GARDU INDUK AREA DURI KOSAMBI
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Hutagalung, D.Fadel Sion
Pramono, Tri Joko
Subject
Teknik Elektro 
Datestamp
2019-12-05 12:51:01 
Abstract :
As one of electrical power transmissionsub systems from power plant to consumers , substasion has an important role which is to elevate voltage from power plant and then proceed to drop voltage from transmission line to consumers.Duri Kosambi substation inter-substations within the area has reliability value the must be maintained so that faults likely causing electrical outage on the consumers do not occur.Transformer on a conventional substation is installed on the Switchyard , therefore it is susceptible ti lightning strike.To protect transformer against lightning surge , lightning arrester is used.Installation of lightning arrester on the substation transformer has to regards several matters , among which are BIL (Basic Insulation Level) from transformer and arrester placement distance itself.According to SPLN 7:1978 the maximum distance between lightning arrester and power transformer for arrester with 150kV rated voltage is less than 80m.While according to the calculation and the condition in switchyard , the distance between arrester and transformer are 37,5m and 3,15m.Corresponding with protection standards , so the transformer protection against lightning surge fault is exceptional. 