A PHP Error was encountered

Severity: Warning

Message: fopen(/home/rama/public_html/application/cache/sessions/rama_sessionu6i9uo7jp2et9esituovoa05p3d62mp8): failed to open stream: No space left on device

Filename: drivers/Session_files_driver.php

Line Number: 174

Backtrace:

File: /home/rama/public_html/application/core/MY_Controller.php
Line: 8
Function: __construct

File: /home/rama/public_html/application/controllers/Document.php
Line: 6
Function: __construct

File: /home/rama/public_html/index.php
Line: 296
Function: require_once

RAMA - REPOSITORY
 DETAIL DOCUMENT
Menentukan Rugi Daya Penyulang Koros Pada Tegangan Menengah 20 KV Di PT. PLN (PERSERO) UP2D Jakarta Menggunakan Software Power Factory 15.1 DigSilent
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Waninghiyun, Mohammad Yuwhent Glenea
Simamora, Yoakim
Subject
Teknik Elektro 
Datestamp
2019-12-05 12:54:11 
Abstract :
This research explores power losses in the 20 kV primary power distribution in the koros feeder using Power Factory 15.1 DigSilent software. Method that used in this research methods, data collection through interviews, observation and documention. In the calculations using Total amount of power losses in the feeder koros is 0,03 MW + 0,02 MVAR or 36,05 kVA, or 0,83 % of the power is sent from the GI Gambir Lama. While large voltage drop of 1,2 % or 0,24 kV of the nominal voltage used is 20 kV distribution network are 5 % and 10 %. It can be assumed that distribution system koros feeder in accordance with the rergulations SPLN. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara

A PHP Error was encountered

Severity: Warning

Message: Unknown: Failed to write session data (user). Please verify that the current setting of session.save_path is correct (/home/rama/public_html/application/cache/sessions)

Filename: Unknown

Line Number: 0

Backtrace: