Abstract :
This research explores power losses in the 20 kV primary power distribution in the koros feeder using Power Factory 15.1 DigSilent software. Method that used in this research methods, data collection through interviews, observation and documention. In the calculations using Total amount of power losses in the feeder koros is 0,03 MW + 0,02 MVAR or 36,05 kVA, or 0,83 % of the power is sent from the GI Gambir Lama. While large voltage drop of 1,2 % or 0,24 kV of the nominal voltage used is 20 kV distribution network are 5 % and 10 %. It can be assumed that distribution system koros feeder in accordance with the rergulations SPLN. 