Abstract :
The transmission line is a very absolute thing in an electric power system. In the transmission of electrical power from the centers of the plant to the burden (consumers), where the distance is far enough then done through the channel tranmission. In this tranmission channel the voltage is raised from the center of the plant through the tranformers to the desired voltage price. In the construction of transmission lines there are several things that must be considered, one of them in the calculation of Sagging. The calculation is used to determine the clearance between the conductor and the Earth, the free distance itself is required for the safety of living beings and transmission equipment. The calculation sagging at 35oC is 2.21 meters while at a temperature of 150oC is 5.14 meters. The clearance in the T52-T53 course is appropriate to the standard set of PERMEN ESDM No. 18 year 2015. 