DETAIL DOCUMENT
PERHITUNGAN KEANDALAN DISTRIBUSI PRIMER 20 KV DI PT.PLN (PERSERO) ULP GENTENG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Wicaksono, David Dwi
Hajar, Ibnu
Subject
Teknik Elektro 
Datestamp
2019-12-19 11:49:51 
Abstract :
PT.PLN (Persero) ULP Tile is supplied by 6 feeders, namely kalibaru feeders, blokagung feeders, Sugihwaras feeders, kaliputih feeders, gambiran feeders, kaligondo feeders. Six ULP Genteng feeders from GI Genteng have 3 units of transformers. Where the results obtained in this study the value of SAIFI in PT.PLN (Persero) ULP tile in each month no more than 2.08 times outages / 6 months which means it meets the SPLN 68-2, 1986 standards and SAIDI values in PT.PLN ( Persero) ULP Tile in each month no more than 13.65 hours / 6 months which means that it meets the SPLN 68-2, 1986 standard. After calculating SAID SAIDI every month, the highest SAIFI SAIDI chart is obtained in May, that is SAIFI 0.057 times and SAIDI 0.00407 hours, which means that it is still in the SPLN 68-2 standard, 1986. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara