Abstract :
System protection power electricity important thing for the system power electricity good for reliability network and keep equipment on the system bro electricity so that
no no broken when there is current interference good that current interference connect short between phase or connect short one phase land . System protection
discussed this is system protection in outgoing feeders with using the GFR relay and calculation current disturbance one phase to soil for determine setting relay in particular feeder in Petukangan substation. After done calculation current
interference one phase to soil get it current interference biggest yes that's 955.86 A and current interference the smallest 762.49 A and from calculation current
interference one phase to soil could in conclusion that increasingly far from source increasingly small current current interference and increasingly close with source
then current interference increasingly great . As for TMS value is 0 , 1 from results calculation and 0.15 of results testing .