REKONFIGURASI JARINGAN SKTM DALAM UPAYA MENEKAN SUSUT TEKNIK PENYULANG DI PT.PLN (PERSERO) AREA CIMAHI
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Prasojo, Abbiyoga
Ispranyoto, Edy
Subject
Teknik Elektro 
Datestamp
2020-01-16 11:57:52 
Abstract :
Loading condition of feeder PCB which supplied from Lagadar substation of Area Cimahi has been overloaded, on the other side, diameter of conductor used on feeder is still 150 mm2 which technically considered unballance to its loading condition. Hence, overloaded condition and small diameter of conductor can pottentially occurs technical losses on PCB feeder and will affect on network reliability as well. To mitigate certain condition, loading on PCB feeder need to be decreased by reconfiguring its load to PCS feeder. Feeder reconfiguration on PCB feeder will be done by transferring some of its load to PCS feeder which loading condition is still underload. The load flow simulation will be a refference to execute reconfiguration on PCB-PCS feeder of area Cimahi 20 kV spindle network. Purpose of this network reconfiguration are to signifficantly lessen technical losses on PCB feeder which will imply to reliability and continuity of electrical supply on network system. 