Abstract :
The short circuit test is the one of type test in SPLN D3 002-1:2007, while IEC 60076-1 qualifying as special test. Based on IEC 60076-5 short circuit endurance is divided to dynamic force and thermal. Dynamic force can be seen with measurement of reactans before and after short circuit test, this based on IEC 60076-5. Thermal in this research can be seen with measurement of resistance before and after short circuit test. This research aims to find correlation between changes of percentage reactance and resistance to winding loss in ditribution transformer. The methode used is a quantitative method, because it has a calculation to process data and produce data in the form of numbers. From the result of this research, reactance not showing any effect on winding loss because change of percentage reactance not show the correlation. But on the resistance can be seen the correlation to the transformer with a capacity of 50 kVA, the resistance of the secondary winding has increased by 3,49%, Then seen the change in percentage loss turns go up, on tap 1 for 2,22%, on tap 3 for 2,162%, and on tap 7 for 2,038%.