DETAIL DOCUMENT
PENGGUNAAN CIRCUIT BREAKER OUTGOING DALAM MENGAMANKAN GANGGUAN PADA SALURAN KABEL TEGANGAN MENENGAH
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Santoso, Oke Rahmat
Pasra, Nurmiati
Subject
Teknik Elektro 
Datestamp
2020-01-16 12:01:48 
Abstract :
Permanent disturbance is a disorder that can not go away by itself, temporary disturbance is a relatively short disturbance, usually caused by lightning strikes, rain, angina, or friction-friction trees near the network. Circuit Breaker Outgoing functioning as an electric circuit breaker and fast-switching under normal circumstances or in disturbances, this cubicle is also known as the cubicle PMT (Power Breaker) is equipped with a protective relay and circuit breaker. This cubicle can also be installed as a limiting device. This cubicle can also be installed as a limiting device. After calculating the impedance of short circuit 1 phase, 2 phase, and 3 phase, then re-setting the CBO with the current relay setting and the correct ground disturbance is the current through the relay = 0.06 A, the current acting on the OCR relay = 0.12 A, and the current works on the OCR moment = 0.6 A. The correct ground fault relay setting is the current working on the relay GFR = 0.15 A, and the current working on the moment GFR = 0.75 A, the TMS working on the OCR is 0.9s and the TMS working on the GFR is 0.8s 
Institution Info

Institut Teknologi Perusahaan Listrik Negara