Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
KURNIAWAN, RIZKI
Erlina, Erlina
Subject
Teknik Elektro
Datestamp
2020-01-16 12:02:36
Abstract :
PMS is one piece of equipment at the mains substation that serves to connect/high voltage decided without any burden. As for slah one component contained a series of control PMS kontaktor is magnetism which is very important in the operation. On a series of common control of damage due to the self inductance kontaktor, to know the magnitude of the self inductance voltage use osciloskop workbench and apliasi. The results of the data before the installation of the diode for 1 to 5 seconds with the source voltage 110VDC becomes 5KVDC, 9KVDC, 12KVDC, 16KVDC, 18KVDC and after doing the installation of the diode reverse bias voltage be steady 110VDC on 1 to 5 seconds. As well as he did with the installation of the diode reverse bias voltage induction themselves into lost/stable and after doing a reverse biased diode installation the operator can operate the PMS/remote operator through space.