DETAIL DOCUMENT
Studi Indeks Keandalan Sistem Distribusi Dengan Nilai SAIFI SAIDI Pada Penyulang F3 Horizon UP3 Bengkulu
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Zagita, Syavia
Koerniawan, Tony
Handayani, Oktaria
Subject
Teknik Elektro 
Datestamp
2022-10-12 01:12:39 
Abstract :
The level of reliability of the distribution system is currently very important, because if a distribution system is declared reliable, it will increase customer satisfaction. The purpose of this thesis are to knowing the reliability index of the F3 Horizon UP3 Bengkulu feeder. This thesis are using SAIDI SAIFI calculation method, we can find out whether the distribution system are reliable or unreliable. If a system is declared unreliable, the optimal solution is to add the fuse and the sectionalizer to the feeder. Because with the addition of these tools, the reliability index of SAIDI and SAIFI values will increasing, If value of the two indexes are smaller, the system will reliable. In this research, the results obtained that SAIDI 1,9062 hours per year and SAIFI 1,6166 times per year with a ratio of SPLN 59: 1985 SAIDI value of 12,842 hours / customer / year and SAIFI 2,415 outages / customer / year. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara