DETAIL DOCUMENT
Pengaruh Ketidakseimbangan Beban Terhadap Arus Netral dan Losses Pada Transformator Distribusi Di PT PLN (Persero) ULP Bogor Kota
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
SOFIYANTI, AYU
Qosim, Muchamad Nur
Pawenary, Pawenary
Subject
Teknik Elektro 
Datestamp
2022-10-04 08:04:44 
Abstract :
An unbalanced load in a system of electricity distribution always occurs in a low voltage grid system this is due to the unequal distribution of load in both the program and the fastness. An unbalanced load creates a current in the neutral conductor. The current that flows in the neutral conductor of this transformer has coused of losses, which is the cost of a neutral current on a transformer neutral conductor. The research discussed the losses from the presence of a neutral current in the transformer neutral conductor using load measurement data at day and night. This research uses the literature study method as a reference for the author and field observations at noon and night load measurements for 7 days at PT PLN (Persero) ULP Bogor city. This data was obtained from one of UNELEC distribution transformer with a capacity of 630 kVA owned PT PLN (Persero) ULP Bogor City. Based on the percentage of the unbalanced factor at noon, the result is 7,17 % and the imposition of imposition at night is obtained is 5,8967 %. Whereas as result losses of a neutral current at neutral conductor neutral is 0,2131 kW with precentage is 0,0397 % and in the night as result is 1,4257 kW with precentage is 0,2662 %. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara