Abstract :
The advancement of science and technology today makes the need for electrical energy to increase among people. Electricity sources distributed by PLN are not all acceptable to the consumer because some are lost in the form of power shrinkage. Losses that occurs due to high voltage fall value.
Therefore, the method of rupture load in the wine represing to reduce the voltage fall and the losses. Calculations are done to fall voltage and the normal strain (losses) is done with the formula manual, but in an era that relies heavily
on technological science and this application can be done using software Etap 12.6 (Electrical Transient And Analysis Program). The purpose of this research is to know the large value of the power line with the Etap 12.6 software after and before the attempt to repair the voltage drop value so that the value of the
power (losses) will also decrease. In large results falling voltage in the anggur recharger represtionation before being broken is 8.1% with a power shrinkage (losses) of 34 8.3 kW and after the load break method fell voltage in the anggur recharger after being broken up that occurs at 1.7% so that the amount of
power (losses) generated is 120 kW.