Kajian SKTM dalam rangka pemeliharaan dengan deteksi Partial Discharge pada penyulang milan di PLN area Bandengan
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Assiddiq M, Ilham
Suwarno, Suwarno
Mowaviq, Muhammad Imbarothur
Subject
Teknik Elektro 
Datestamp
2022-10-04 04:40:42 
Abstract :
In the distribution system in Jakarta, almost entirely ground cables are used for the medium voltage system. The use of ground cables for distribution systems can increase aesthetic value, but it raises problems, namely interference from internal and external factors. Therefore, it is necessary to do cable testing to determine the condition of the ground cable. Partial discharge testing in this study uses the Oschillating wave test system (OWTS), OWTS here will fire the DAC (Damped Alternating Current) voltage, then the Partial Discharge will be read on the computer. The SKTM that was tested at the PP76 substation to Pondok Indah GI contained Partial Discharge in phase 2 at a length of 4249 m, the detected partial discharge was still in a good enough status according to PLN policy standards and needed to be re-detected within the next 24 months. 