DETAIL DOCUMENT
PENGARUH BEBAN TIDAK SEIMBANG TERHADAP ARUS NETRAL DAN LOSSES PADA SALURAN GARDU DISTRIBUSI BJ38A PT PLN (Persero) ULP BINJAI KOTA
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
RAUDAH, SALSA NARA
Purwanto, Sugeng
Subject
Teknik Elektro 
Datestamp
2022-10-03 04:32:34 
Abstract :
The load imbalance in an electrical distribution system occurs due to the different ignition timing of electrical energy in each electricity consumer. The imbalance occurs in singlephase loads, namely in the R, S and T phases. So in this study, it is necessary to balance the load using the load equalization method so that the load becomes balanced. The BJ38A substation experienced a load imbalance of 15.3667% after balancing the load, the load imbalance decreased to 2.615%. The percentage of losses in neutral conductors is 0.984% to 0.0133%. It can be said that load balancing with the load equalization method is quite effective in reducing the value of losses for BJ38A distribution substation customers. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara