Studi Hasil Pengukuran Tahanan Pentanahan Pada Peralatan di Switchyard Gardu Induk Angke PT.PLN (Persero) UIT – JBB UPT Duri Kosambi
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Romadani, Dela
Hajar, Ibnu
Subject
Teknik Elektro 
Datestamp
2022-10-03 03:57:27 
Abstract :
Substation is part of the electric power system that distributes electrical energy from the generator to the load. It is necessary to safeguard against the danger of interference to provide safety and security guarantees for the installed equipment and humans at the Substation. This final project discusses the study of the results of measuring grounding resistance on equipment in the switchyard with quantitative methods based on the results of measuring equipment grounding resistance, step voltage, touch voltage. The qualitative method is based on the quality of the equipment grounding resistance at the Angke Substation switchyard. The value of the equipment grounding resistance at the substation must be able to meet the IEEE Std standard. 80 ? 2000 is < 1 ?. The smaller the ground value obtained, the better the grounding. Based on the results of the final project research, the value of the grounding resistance of the Angke Substation is 0.13 V. The value of the touch voltage is 651.55 V for humans weighing 70 kg and 481.4 V for humans weighing 50 kg. With the value of the permissible touch voltage is 626 V. The step voltage value is 2135.2 V for a human weighing 70 kg, and 1577.6 V for a human weighing 50 kg. With a permissible step voltage value of 2216 V. 