UPAYA PENYEIMBANGAN BEBAN TRANSFORMATOR GARDU DISTRIBUSI SJPP DI PT. PLN (PERSERO) ULP DEPOK KOTA DENGAN METODE PECAH BEBAN
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Rahmawati, Kurnia
Erlina, Erlina
Subject
Teknik Elektro 
Datestamp
2022-09-30 06:50:39 
Abstract :
A good electrical power system should have a voltage value that does not exceed ba-bag tolerance. Allowable tolerance limit for a voltage value of +5% and -10% of its face value (spln 1 : 1995). The large demand for loads and unstable load conditions and the distance between the load location and the distribution center that is far away resulted in problems in the distribution of electrical power, especially the problem of falling voltage. To reduce the fall in voltage at the end of the refiner is carried out voltage repair by the method of load rupture and load equalization. In this final project discussed falling voltage at the sjpp distribution substation major 2. From the inspection result of the tip voltage obtained obtained prosen fall voltage of 9.565% which means that it is close to the tolerance limit of spln 1:1995 which is +5% and -10%, it is necessary to make improvements. In the calculation result, the voltage fall after repair by the method of load rupture and load equalization is still within the tolerance limit of spln 1:1995 which is +5% and -10%. 