Abstract :
In the distribution of electrical energy there are several problems that are often faced in distribution transformers, the transformer has a voltage drop at the end of the line exceeding 10%. The voltage drop permitted by PLN should not exceed -10% and +5% in accordance with SPLN 1: 1995. Because if the voltage drop exceeds the PLN standard, the impact can affect the quality of service to customers. The method in this thesis uses quantitative methods. At PT. PLN (Persero) ULP Karang Bandar Lampung has a transformer that has a voltage drop at the end of the line for each phase of 27.2%, 18.1%, and 16.3% in the dry feeder at the K606 substation. After maneuvering the load to the K1045 substation, the voltage drop at the end of the line for each phase was 3.1%, 2.2%, and 0.9%. In this case, it can be proved that the load maneuver is a good enough method to overcome the voltage drop at the K606 substation. Therefore, because the voltage drop is in accordance with the standard limit of SPLN 1: 1995, the distribution of electricity can be properly distributed to customers. 