DETAIL DOCUMENT
ANALISA RELOKASI RECLOSER UNTUK MENURUNKAN NILAI SAIDI SAIFI DENGAN METODE SECTION TECHNIQUE PADA JARINGAN DISTRIBUSI 20KV PENYULANG CITARIK
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Fadli, Yogi Darul
Samsurizal, Samsurizal
Subject
Teknik Elektro 
Datestamp
2022-09-28 03:41:06 
Abstract :
The distribution network is the part of the electric power system that is closest to the customer. The reliability of each component of the distribution system equipment can affect the continuity of power service. This study aims to evaluate the reliability of the distribution system at the Citarik Feeder and to improve the system reliability index. The method used is the section technique method and the reliability index values for the Citarik Feeder are obtained, namely SAIFI 1.08958323 faults per customer.year, SAIDI 12.9958323 hours per customer.year. Calculations using ETAP existing conditions, Citarik Feeder SAIFI 1.0679 faults per customer.year, SAIDI 12.9629 hours per customer.year. To increase reliability, a recloser was implemented on the feeder and the most optimal reliability index was obtained, namely, Citarik Feeder SAIFI 0.9885 faults per customer.year, SAIDI 12.8447 hours per customer.year 
Institution Info

Institut Teknologi Perusahaan Listrik Negara