ANALISIS JATUH TEGANGAN PADA JARINGAN DISTRIBUSI PENYULANG TANJUNG SELOR 1 DI P.T PLN (PERSERO) ULP TANJUNG SELOR KALIMANTAN UTARA
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Krismayanti, Anggi
Budi, Purnomo Willy
Sitorus, Meyhart Torsna Bangkit
Subject
Teknik Elektro 
Datestamp
2022-09-28 03:25:38 
Abstract :
The distribution system at the Tanjung Selor 1 feeder at P.T PLN ULP Tanjung Selor uses a radial system. In some of these channels there is a voltage drop that exceeds the standard limit, according to SPLN number 7 of 1987, which is 5%. To determine the voltage drop on the feeder, it is done by calculating the voltage drop per point (section), by dividing the Tanjung Selor 1 feeder into 3 branching points. This 3 branching point division aims to see the highest voltage drop. From the results of the analysis at points A, B, and C, the calculation results at point A are 415.96 V, then at point B are 800.23 V, and at point C are 1.333.78 Volts. So the one that has the largest voltage drop is at point C, where point C has the longest line, because a network that is too long will have enough resistance, so that the energy channeled will be reduced and will be losses. The solution is to replace the cross-section of the conducting wire, because the small size of the conductor has a large resistance so that the voltage drop that occurs will be large as well. By increasing the cross-section of the conducting wire, a smaller resistance value can reduce the value of the voltage drop 