Abstract :
The reliability of the electric power system can be seen from the continuity of electric power service. Although the reliability of an energy system can be defined as the ability of the system to provide power of satisfactory quality. The purpose of this study is to analyze the results of the calculation of the reliability index values of SAIDI, SAIFI and CAIDI and the results of the comparison of the reliability index values obtained through the Section Technique Method with SPLN 86-2: 1986. The impact of individual equipment constraints is systematically identified by analyzing what happened. on the system if there is a problem with the installed equipment. Every equipment failure is analyzed from all load points. In this study, the results of the calculation of the reliability index of the West City ULP distribution system were found within the organizational scope of PT PLN (PERSERO) UP3 PEKANBARU. By using the Section Technique method, the SAIDI value is 24,339 hours/year, the SAIFI value is 8.1127 times/year and the last and the CAIDI value is 6 hours/interference. 