KAJIAN GANGGUAN JOINTING TERHADAP INDEKS KEANDALAN DI SISTEM DISTRIBUSI DAN ENERGI TAK TERSALURKAN PADA PENYULANG DI PT.PLN (PERSERO) UP3 PONDOK KOPI
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
JOELIO ABROR T, MUHAMMAD
Qosim, Muchamad Nur
Subject
Teknik Elektro 
Datestamp
2022-10-11 04:34:42 
Abstract :
Disturbance in jointing is one of the most common disturbances in SKTM which is handled by PT. PLN (Persero) UP3 Pondok Kopi. This interference can also cause reduced reliability in the distribution of electric power. The purpose of this study was to determine SAIDI and SAIFI due to jointing disturbances at PT. PLN (Persero) UP3 Pondok Kopi and Energy Not Supplied (ENS) due to these disturbances and to determine the percentage effect of jointing disturbances on distribution system reliability. The data analysis method used in this study was to calculate the SAIDI and SAIFI index values and also calculate the ENS due to jointing disorders. From the calculation results, the SAIDI value due to jointing disturbances is 0.154 hours/year and the SAIFI value is 0.18 blackouts/year, it can be said that the reliability in the distribution of electricity at PT. PLN UP3 Pondok Kopi is still categorized as reliable. 