Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Fitri, Farah Annisa
Pawenary, Pawenary
Subject
Teknik Elektro
Datestamp
2022-10-27 02:39:56
Abstract :
The installation of cover FCO on the SUTM network at the Tambun branch is to minimize energy that is not channeled to customers and losses experienced by PLN, because when the Tambun branch experiences disturbances such as phase to phase short circuit currents and animals are exposed to the SUTM network, then when it goes out in The Tambun branch will spread to the Mustika Jaya feeder because there is no FCO cover installed on the Tambun branch, after the FCO cover is installed at the branch, then if there is a disturbance in the Tambun branch, only the branch will be extinguished. The energy that was not distributed to customers before the installation of the FCO cover at the Tambun branch which occurred 2 times was 2,949,823kWh, while after the installation of the FCO cover at the Tambun branch, the energy that was not channeled to the customer was 116,482.73kWh, and before the installation of the FCO cover at the Tambun branch, the loss experienced by PLN in 2020 in 1 year was 4,261,609,288 rupiah, and after the installation of the FCO cover at the Tambun branch, the loss experienced by PLN in that 1 year was 168,282,519 rupiah.