PERBAIKAN JATUH TEGANGAN PELANGGAN BSD VILLA SERPONG BERDASARKAN KAJIAN KELAYAKAN OPERASI DAN INVESTASI
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Astuti, Anin Tsaaniyah
Pasra, Nurmiati
Subject
Teknik Elektro 
Datestamp
2022-10-28 01:45:13 
Abstract :
The voltage drop is the difference between the receiving voltage and the transmit voltage. Where this voltage drop can be due to a network that is too long so that it increases the value of losses. It is said that the voltage drop is if the voltage value drops more than 10% of the nominal voltage according to SPLN No.1 of 1995. From the data analysis, the voltage drop starts from the S-phase panel 5 majoring B with the supply of the SR183 substation, which is 11.88%. In the repair, you can look for the nearest substation or add additional substations. By looking for the nearest substation the voltage drop value in panel 5 is reduced to 0.39% in the R phase, 0.59% in the S phase and 0.68% in the T phase. Meanwhile, with the addition of the insertion substation the voltage drop value is reduced to 0.015% in the R phase, 0.024% in the S phase and 0.027% in the T phase. Both repair methods are operationally feasible because they can improve the value of the voltage drop. On the investment side, it is known that the repair method by finding the nearest substation is investment-worthy where NPV>0, IRR>Discount Rate, B/C>1, and PBP<5 years, while the repair method with the addition of a substation is not investment-worthy where NPV<0 , IRR5 years. Therefore, in repairing the voltage drop, customers at BSD Villa Serpong can use the first method, which is to find the nearest substation. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara