Abstract :
Ventilation as a building's air conditioning system has an important role in
controlling temperature, air humidity, air quality and air movement. The function
of ventilation, apart from producing clean air, also functions to remove polluting
gases (contaminants). This research is entitled "ANALYSIS OF AIR
VENTILATION DESIGN ON COMFORT FEASIBILITY IN PT. Organic
Compounds (VOC). The method used in this research is a quantitative method
with a descriptive approach. By using GVR calculations in accordance with SNI
standards regarding procedures for designing ventilation systems (SNI 03-6572
(2001)). This research was carried out using an anemometer and an air quality
detector to find wind speed, temperature and air quality values. The research
results from a room area of 22 m² with a total of 5 employees and 1 exhaust fan
and 1 AC and without natural ventilation in the form of windows had a room
temperature of 30?C and humidity of 54% showed that the condition of the room
was less comfortable. The existing ventilation in a room measuring 22 m² shows
that the air ventilation in the production room does not meet existing standards,
which should have a total ventilation area of 10% of the floor area, namely 2.2 m².
So in this case it is necessary to add natural ventilation in the form of casement
windows with a size of 0.6x1.5, 2 pieces and also replace the exhaust fan with a
size of 0.7x0.7 m, 1 piece