Abstract :
Most of the blackout in an electric power system is due to problems that occur in the distribution system, so it is necessary to measure the reliability index. This analysis aims to evaluate the reliability of the Kikim redistribution system in the Juaro River parent garrison using the Section Technique method. THE result of the calculation obtained by SAIDI value 8.67 hours/year, SAIFI amounted to 2.954 times/year and CAIDI amounting to 2.93 hours/year. Based on the SPLN No. 59:1985, THE value of SAIDI is 21 hours/year, SAIFI amounted to 3.2 times/year and CAIDI of 6.56 hours/year. Kikim's refills meet PLN standards for SAIFI, SAIDI, and CAIDI grades.
Keywords : Reliability, Section Technique, SAIFI, SAIDI, CAIDI