DETAIL DOCUMENT
STUDI PENGARUH KETTIDAKNORMALAN PENGUKURAN KWH METER PADA PELANGGAN TEGANGAN RENDAH 3 PHASE DI PT. PLN (PERSERO) UP3 CENGKARENG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Gihon Siagian, Faber Agustinus
Samsurizal, Samsurizal
Widyastuti, Chistine
Subject
Teknik Elektro 
Datestamp
2022-10-10 08:04:46 
Abstract :
Measuring the electrical energy is an important thing to do in PT.PLN. UP3 Cengkareng is using the Automatic Meter Reading (AMR) system for monitoring, recording the stand meter, and reporting the data into the software data management. An electrical meter with an AMR system can be used as a data abnormality detector for electrical problems. AMR system will detect the consumers' electrical usage data, starting from the data before the wiring error occurred and after the wiring error occurred accurately. So both consumers and PLN will know how many kWh meter values that aren't billed. In this research, From the AMR downloaded data, kWh imported data should be with no value, but it has some value and billed due to wiring error from Phase 3 of kWh importation. From this research, we discovered that there was a phase reversal and it could be seen from the phasor diagram where the S phase angle was from 168,30 to 14,40. On the other hand, the stand meter became minus. So that after the calculation, the next bill is 41538,8 kWh or as equal as Rp. 60.949.050,- 
Institution Info

Institut Teknologi Perusahaan Listrik Negara