Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
David, Rivai
Willy, Purnomo
Subject
Teknik Elektro
Datestamp
2019-10-10 09:45:34
Abstract :
Sulfur Hexafluoride (SF6) is a gas that can be used as an isolation medium in electrical equipment, as well as used in Gas Insulated Switchgear (GIS) in electric power transmission systems. SF6 gas quality affects performance as an
isolation medium. SF6 gas quality parameters can be seen from the physical condition of the gas, namely Purity, Moisture Content, Dew Point, and Decomposition Product. SF6 gas quality is analyzed with SF6 Analyzer test
equipment.. Based on the measurement results and the average for each GIS New Senayan compartment, An Introduction to Kembangan I GIS, which has Purity 98%; Moisture Content >1000 ppmV; Dew Point 3 ° C and replace
Absorbent on CT equipment, DS Rail 1 & 2, DS Line so that the insulation strength does not decrease. An introduction to Kembangan II GIS, which has Purity 99%; Moisture Content >1000 ppmV; Dew Point 4 ° C and replace Absorbent on CT equipment, DS Rail 1 & 2, DS Line so that the insulation
strength does not decrease. GIS Transformer 1, which has Purity 99%; Moisture Content >1000 ppmV; Dew Point 3 ° C and do replacement Absorbent on CT equipment, DS Phase 1 Rail (S, T) & DS Rel 2, DS Line so that the insulation
strength does not decrease. GIS Transformer 2, which has 99% Purity; Moisture Content >1000 ppmV; Dew Point 2 ° C and replace Absorbent on CT equipment, DS Rail 1 & 2, DS Line so that the insulation strength does not decrease. GIS
Transformer 3, which has Purity 99%; Moisture Content >1000 ppmV; Dew Point 2 ° C and replace Absorbent on CT equipment, DS Rail 1 & 2, DS Line Phase T so that the insulation strength does not decrease. Coupling GIS, which has Purity 99%; Moisture Content >1000 ppmV; Dew Point 5 ° C and replace Absorbent on CT equipment, DS Rail 1 Phase R, T & DS Rel 2, DS Line so that the insulation strength does not decrease.